Exciter Model: ST6C_PTI

 

Model Equations and/or Block Diagrams

Parameters:

OEL OEL input: if < 2, add to error signal; if = 2, LV gate 1; if = 3, Sum after LV gate 1; if = 4, LV gate 2
UEL UEL input: if < 2, add to error signal; if = 2, HV gate 1; if = 3, Sum after LV gate 1; if = 4, HV gate 2
SCL SCL input: if < 2, add to error signal; if = 2, Take Over 1; if = 3, Sum after LV gate 1; if = 4, Take Over 2
SW1 Logical switch 1 (1 = Position A, 2 = Position B)
Tr Filter time constant, sec.
Kpa Regulator proportional gain, p.u. (> 0.)
Kia Regulator integral gain, sec-1(> 0.)
Kda Regulator derivative gain
Tda Regulator derivative channel time constant
VaMax PI maximum output, p.u.
VaMin PI minimum output, p.u.
Kff Feedforward gain, p.u.
Km Main gain, p.u.
Kcl Field current limiter conversion factor
Klr Field current limiter gain, p.u.
Ilr Field current limiter setpoint, p.u.
Vrmax Maximum regulator output, p.u.
Vrmin Minimum regulator output, p.u.
Kg Feedback gain p.u.
Tg Feedback time constant, sec.
VmMax Model Parameters\VmMax
VmMin Model Parameters\VmMin
Ta Voltage regulator time constant, sec
Kp Potential source gain, pu
Ki Current source gain, pu
Xl P-bar leakage reactance, pu
ThetaPDeg Phase angle of potential source, degrees
Kc Rectifier regulation factor, pu
VbMax Maximum excitation voltage, pu